COPPER BRAZED PLATE HEAT EXCHANGER SUBSTATIONS
Model "Milano"
From 50 to 1.500 kW


Copper brazed plate heat exchangers.
50 to 1.500 kW standard package.
With heat meter, control and security devices.
PN 25 on primary circuit.
Twin heat exchangers version (max 5.000 kW).
For hot and superheated water networks.
Heating, cooling and DHW versions.
User customizable. CE / PED Certification.
Small size. Easy to disassemble and move.
Ready for remote metering and remote control.
Flow rate, power and return temperature limitation.
Temperature management for fixed-point or external temperature compensated.
Our models
Hot Water , Heating
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
105 |
MILANO 50 C |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
106 |
MILANO 75 C |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
107 |
MILANO 100 C |
100.00 |
25/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
157 |
108 |
MILANO 125 C |
125.00 |
25/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
170 |
109 |
MILANO 150 C |
150.00 |
40/25 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
175 |
110 |
MILANO 175 C |
175.00 |
40/25 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
179 |
111 |
MILANO 200 C |
200.00 |
40/40 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
179 |
112 |
MILANO 250 C |
250.00 |
40/40 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
195 |
113 |
MILANO 300 C |
300.00 |
40/40 |
65/65 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
199 |
114 |
MILANO 350 C |
350.00 |
40/40 |
65/65 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
236 |
Hot Water , DHW - Direct
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
115 |
MILANO 50 C ACS D |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
116 |
MILANO 75 C ACS D |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
117 |
MILANO 100 C ACS D |
100.00 |
25/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
118 |
MILANO 150 C ACS D |
150.00 |
40/25 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
170 |
119 |
MILANO 200 C ACS D |
200.00 |
40/40 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
175 |
120 |
MILANO 300 C ACS D |
300.00 |
40/40 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
191 |
Hot Water , DHW - Indirect
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
121 |
MILANO 50 C ACS I |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
153 |
122 |
MILANO 75 C ACS I |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
157 |
123 |
MILANO 100 C ACS I |
100.00 |
25/20 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
157 |
124 |
MILANO 150 C ACS I |
150.00 |
40/25 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
175 |
125 |
MILANO 200 C ACS I |
200.00 |
40/40 |
50/50 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
184 |
126 |
MILANO 300 C ACS I |
300.00 |
40/40 |
65/65 |
25.00 |
10.00 |
110 |
95 |
1500x500x1835 |
204 |
Hot Water , Heating
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
127 |
MILANO 400 C |
400.00 |
40/50 |
80/80 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
287 |
128 |
MILANO 500 C |
500.00 |
50/50 |
80/80 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
321 |
129 |
MILANO 600 C |
600.00 |
50/65 |
80/80 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
339 |
130 |
MILANO 700 C |
700.00 |
50/65 |
80/80 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
373 |
131 |
MILANO 800 C |
800.00 |
65/65 |
100/100 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
373 |
132 |
MILANO 900 C |
900.00 |
65/65 |
100/100 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
419 |
133 |
MILANO 1000 C |
1000.00 |
65/65 |
100/100 |
25.00 |
10.00 |
110 |
95 |
1800x870x1650 |
419 |
Overheated Water , DHW - Direct
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
141 |
MILANO 50 S ACS D |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
142 |
MILANO 75 S ACS D |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
143 |
MILANO 100 S ACS D |
100.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
144 |
MILANO 150 S ACS D |
150.00 |
25/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
154 |
145 |
MILANO 200 S ACS D |
200.00 |
25/25 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
171 |
146 |
MILANO 300 S ACS D |
300.00 |
25/25 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
171 |
147 |
MILANO 400 S ACS D |
400.00 |
25/40 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
183 |
148 |
MILANO 500 S ACS D |
500.00 |
40/40 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
187 |
Overheated Water , DHW - Indirect
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
149 |
MILANO 50 S ACS I |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
150 |
MILANO 75 S ACS I |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
151 |
MILANO 100 S ACS I |
100.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
152 |
MILANO 150 S ACS I |
150.00 |
25/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
158 |
153 |
MILANO 200 S ACS I |
200.00 |
25/25 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
176 |
154 |
MILANO 300 S ACS I |
300.00 |
25/25 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
180 |
155 |
MILANO 400 S ACS I |
400.00 |
25/40 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
196 |
156 |
MILANO 500 S ACS I |
500.00 |
40/40 |
80/80 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
205 |
Overheated Water , Heating
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
157 |
MILANO 50 S |
50.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
158 |
MILANO 75 S |
75.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
159 |
MILANO 100 S |
100.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
141 |
160 |
MILANO 125 S |
125.00 |
20/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
158 |
161 |
MILANO 150 S |
150.00 |
25/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
158 |
162 |
MILANO 175 S |
175.00 |
25/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
163 |
163 |
MILANO 200 S |
200.00 |
40/20 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
176 |
164 |
MILANO 250 S |
250.00 |
25/25 |
50/50 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
180 |
165 |
MILANO 300 S |
300.00 |
25/25 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
185 |
166 |
MILANO 350 S |
350.00 |
40/25 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
189 |
167 |
MILANO 400 S |
400.00 |
25/40 |
65/65 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
196 |
168 |
MILANO 500 S |
500.00 |
40/40 |
80/80 |
25.00 |
10.00 |
130 |
95 |
1500x500x1835 |
200 |
Overheated Water , Heating
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pos. |
Model |
Power |
DN 1° |
DN 2° |
PN 1° |
PN 2° |
Tmax 1° |
Tmax 2° |
Dimensions |
Weight |
169 |
MILANO 600 S |
600.00 |
40/40 |
80/80 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
287 |
170 |
MILANO 700 S |
700.00 |
40/50 |
80/80 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
287 |
171 |
MILANO 800 S |
800.00 |
40/50 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
321 |
172 |
MILANO 900 S |
900.00 |
40/50 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
321 |
173 |
MILANO 1000 S |
1000.00 |
40/50 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
353 |
174 |
MILANO 1150 S |
1150.00 |
40/65 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
373 |
175 |
MILANO 1300 S |
1300.00 |
50/65 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
419 |
176 |
MILANO 1500 S |
1500.00 |
50/65 |
100/100 |
25.00 |
10.00 |
130 |
95 |
1800x870x1650 |
450 |
Strength
range and performances
- Complete range from 50 to 6000 kW for district heating and DHW with hot and superheated water networks.
- Ready in stock delivery ready for standard models.
- Mass production ensures high quality level.
- Numerous options available.
construction
- Extremely compact, easy to transport and install.
- Mechanical design primary circuit: PN 25/135 °C standard.
- Primary circuit in accordante with high quality industrial standards (ASTM A106 GR B, tig welded with CE/PED certified x-ray).
- Wells for probes and instruments in Inox AISI 316L steel and flat sealing gasket with Teflon.
- Ready for drainage filter (serial and parallel).
- Ready for installation of optional booster pump.
- Pressure switch and temperature gauges on all circuits.
- Vents and drains on all circuits.
- Special shutter regulation valves for anti-noise district heating applications even with very high deltaP values.
- Galvanization treatment on secondary circuit.
- Metal control board IP 55 with double lock.
- Heat meter inside control board.
- CE/PED approved including also heat exchanger rupture.
- Extension of CE / PED certification to the whole set "Power Station", as an alternative to the Ispesl procedures.
- Wiring and probe cable protected by sheath.
- Amarc DHS components supplier: ALFA LAVAL (heat exchangers) | SIEMENS (heat meters, regulation valves, actuators) | KAMSTRUP (heat meters) | KSB (valves and check valves) | NAVAL OY (ball valves) | IVR (shut-off valves) | CALEFFI (security valve) | SAMSON (self-operated valves) | SALMSON (pumps) | HONEYWELL (actuators, 2-3 port valve)
management
special functions and services
- Metering system sealing and safety lock especially on probes.
- Technical assistance and training.
- Internal Service specialized in district heating with availability on-call service 24/24 h.
- Electrical and mechanical installation.
- Transport and positioning.
- Substation pre-sizing tool application.
- Specifications, diagrams and drawings.
- Preset typical insatallation schemes available.
Common schematic
Working condition
HOT WATER | SUPERHEATED WATER | COOLING | DIRECT H.D.W. (Hot Domestic Water) | INDIRECT H.D.W. (Hot Domestic Water) | |
---|---|---|---|---|---|
THERMAL DESIGN | 90/65°C | 115/65°C | 7/11°C | 85/55°C | 85/55°C |
THERMAL DESIGN | 60/75°C | 60/75°C | 14/8°C | 25/50°C | 30/55°C |
PRESSURE LOSS (Δp) @ NOMINAL CONDITIONS - CIRCUITS 1 & 2 | < 10 w.c.m. (1°) < 3 w.c.m.(2°) | < 10 w.c.m. (1°) < 3 w.c.m. (2°) | < 15 w.c.m. (1°) < 6 w.c.m. (2°) | < 10 w.c.m. (1°) < 3 w.c.m. (2°) | < 10 w.c.m. (1°) < 3 w.c.m. (2°) |
MECHANICAL DESIGN | PN25 PN16 | PN16 PN10 | PN25 PN10 | ||
THERMAL OVERSIZING | 20% | ||||
CERTIFICATION DESIGN | CE/PED - ISPESL | ||||
Δp EMERGENCY CLOSEDOWN | 25 barg | ||||
OPTIMIZATIONS | FLOW RATE LIMITATION, REMOTE SIMULTANEOUS TEMPERATURE AND POWER SETTING |